Operating Instructions Diagnostic Unit
I
Functions
6510 046
Type Type No.
..B operation phase
运行阶段
Significance:
Frequency levels of error:
含义:故障频繁度
Level 1 infrequent
1 度不频繁发
生
Error code number
故障代码
Level
10 frequent
10 度频繁发生
Erro
r
Error description
Causes, remedy or instructions
BW
01
XX
Interlock contact RK or RKD is
jamming in landing XX.
门锁触点 RK
或 RKD 在 XX 楼层处卡住/在 XX 层检查门锁触点
或门的机械部件。在任务特性程序中必须将门的
型号编程输入
Check interlock contact or
mechanical parts of door in landing
XX.
A correct door type must be
programmed in the job-specific
program.
6
02 01 Calls inhibited via monitoring
召唤因监控作用被禁止
An 8-kbyte RAM is required in CPU.
CPU 中需要一块 8-KBYTE RAM
1
02 02 Quasi ZSE in lift-specific program
released, but Siemens CPU still
used.
在电梯特性程序中 QUASI 的 ZSE 开关被删掉,
但在 SIEMENS 的 CPU 中仍使用
Use Thyssen CPU with battery-backed
RAM chip (storage of position in the
event of power failure or if HS is
switched off).
用 THYSSEN 的 CPU 后备电池的
RAM 芯片(停电或 HS 断开时存储位置信息)
1
02 03 TCM control
TCM 控制
8 k-RAM not recognized; F8 00 will
follow
8K-RAM 未识别;随之以 F800
1
02 04 TCM control
TCM 控制
8 k-EPROM not recognized; F8 00 will
follow
8K-EPRAM 未识别;随之以 F800
1
02 80 Undefined or wrong operation
phase
未定义或错误的运行阶段
1
03 01 No provision has been madefor
disconnect landing in lift-specific
program.
在电梯特性程序中没有编入关梯楼层
Disconnect landing not programmed
(check data sheet) or incorrect order
number on lift-specific EPROM.
关梯楼层
未编程(检查数据表)或电梯特性 EPROM 中的定
单号不正确
1
03 02 No provision has been made for
parking landing in lift-specific
program.
在电梯特性程序中没有编入停泊楼层
Parking landing not programmed,
etc., same as for error 03 01.
停泊楼层未编程
03 03 No provision has been made for
fireman’s landing in lift specific
program.
在电梯特性程序中没有编入消防员楼层
Fireman’s landing not programmed,
etc., same as for error 03 01.
消防员
楼层未编程
04
NN
TCI: error caused by solenoid
switch ZSE.
由磁开关 ZSE 引起的故障/CPU 检查是否有一个
以上 ZSE 开关动作,如果是则停梯并故障连续
储存 4
次/检查 ZSE 开关/参考来自 21 页的说明
TCI: CPU checks whether more than
one ZSE switch is actuated. If so, the
lift will be stopped and error 04 NN
stored four times in succession.
Check ZSE solenoid switch.
SM3
04
XX
TCM: error caused by soldenoid
switch ZSE.
由磁开关 ZSE 引起的故障/CPU 检查是否有一个
以上 ZSE 开关动作,所有 ZSE 动作的楼层 XX
都会显示/检查 ZSE 开关/例如消防员梯
CPU checks whether more than one
ZSE switch is actuated. All landings
XX with ZSE actuated will be
displayed. Check ZSE solenoid
switch, for example fireman’s lift.
05 YY Incorrect computer request by
group (circuit board MG defective
TCI: Check circuit board MG or group
connection (round cable or flat
2
Prepared by:
Keinz
Date of-
Changes: GEGORL
Issuing Dept.:
QMS
issue:
07.02
Revision
D6510-046-B-
E.doc
Page:
2