background image

摘要:选煤厂电气工程设计设计的因素较多,不仅包括着配电室的设计、也包括低压配电系
统之中关于电压等级的设计、变压器结线组别的设计以及照明灯具的接地设计,其设计的科
学性关乎着洗煤厂的用电安全,下面就根据电压等级的设计、变压器结线组别的设计以及照
明灯具的接地设计对选煤厂电气工程设计进行探讨。

 

  关键词:选煤厂;电气工程设计;有关问题

 

  

Abstract:  there are  many  factors of electrical engineering design  for  coal preparation  plant 

design,  not  only  including  also  includes  the  design,  distribution  room  of  the  low-voltage 
distribution system design, the voltage transformer connection group design and lighting earthing 
design, scientific design for the safe use of electricity coal preparation plant, below according to 
design, voltage transformer connection group design and lighting design of grounding of electrical 
engineering design of coal preparation plant. 
  

Keywords: coal preparation plant; electrical engineering design problems 

  

[中图分类号] TV52 1 [文献标识码]A[文章编号] 

  

 

  一、引言

 

  选煤厂中电气工程的设计是选煤厂设计的重要组成部分,其科学性关乎着选煤厂日后
的使用安全性,选煤厂电气工程的设计要求相对较高,关于其具体的设计要求国家相关部
门有着明确的规定,在选煤厂电气工程的设计过程中,不仅要严格的遵循国家相关的设计
规程,也要考虑到选煤厂的实际情况,根据选煤厂的具体情况进行设计,保证设计的质量
以及后续使用的安全。

 

  二、选煤厂电气工程设计的有关问题

 

  (一)选煤厂配电室的设计

 

  选煤厂配电室的设计是电气工程设计中的重要组成部分,对于配电室的设计以及电气
设备的设计要严格的遵循《煤炭洗选工程设计规范》中的规定要求来进行,此外,对于选煤
厂配电室的设计不仅要按照规定要求来进行,还要考虑到选煤厂的实际环境,对于选煤厂
内部的原煤准备车间、易发生火灾和爆炸的场所、原煤仓等煤尘聚集的区域,要严格的按照

《特殊环境电气设计规范》来进行,对于安装电气设备的房间,其出口应该通向无火灾以及

无爆炸危险的环境中,如果安装电气设备的房间必须要与有爆炸危险的环境相通时,那么
在设计的时候一定要注意,电气设备安装的房建必须要保证相对正压,以避免安全事故的
发生。此外,对于配电室房间位置的设置,尽量将其安排在一层,并将门朝向车间外,在配
电室与车间之中设置实体墙相隔,如果一层没有位置设置配电室,必须要设置到车将的上
层时,那么就需要优先将配电室设计在厂房的旁边,保证配电室可以与车间分开设置,并
在室外设置好出入配电室的门,如果由于客观环境的限制必须将配电室设置在车间中部时
且配电室的出口必须与危险环境相连时,就要根据规范设计的要求,在配电室中安装好强
制通风设施,保证工作环境的安全。

 

  (二)低压配电系统之中关于电压等级的设计

 

  一般情况下,我国选煤厂低压配电系统电压等级包括

380V 以及 660V 两种,大中型的

洗煤厂一般都是使用

660V 的低压配电系统,在选用 660V 的低压配电系统时,变压器是通

过中性点电阻接地,并设置了相关的漏电保护装置,在

660V 的低电压配电系统的设计中

要注意,对于塑壳断路器的选择一定要满足规定的标准要求,在选择时,要核对厂家的设
计数值,看其参数能否满足设计规定要求;同时,做好漏电保护的选择,对于漏电保护的
设计可以分为三级,第一级就是在回路中加装漏电保护装置,也就是在供电系统末端增加
漏电保护装置,第二级就是在配电出口处增加漏电保护装置,第三级就是在变压器中性点
中增加漏电保护装置,在实际的设置过程中,要根据动作电流的差别进行选择性设计,保