3.
金 工 车 间 照 明
车 间 面 积
:(60*24) ㎡ =1440
㎡
设 备 容 量
Pe
=112*(440)w=17.28kw
kd =1
tan φ =0
cos φ =1.0
P 30 = kd * Pe =1*17.28=17.28kw Q 30 = P 30 * tan φ =0
(2)
全
厂
低
压
侧
负
荷
: P 30(2) =0.9∑ P30
=0.9*(24.94+12.33+17.28+250+80+20+20)=382.1kw Q 30(2) =0.9∑ Q 30
=0.9*(43.5+21.33+110+90+20+15)=269.53kvar S 30(2) =
382.12 + 269.532 =467.6kva
变 压器 损耗
PT =0.015* S 30(2) =0.015*467.6=7.01KW QT =0.06* S 30(2)
=0.06*467.6=28.06kvar (3) 补 偿 前 全 厂 总 的 负 荷 : P 30(1) = P 30(2) + PT
=382.1+7.01=389.11Kw Q30(1) = Q 30(2) + QT =269.53+28.06=297.59Kvar
S 30(1) =
P 2 30(1) + Q 2 30(1) =489.86Kva
cos φ = P 30(1) / S 30(1) =389.11/489.86=0.79<0.9 (4)需要电容补偿
Qc = p′30 *(tan φ -tan ′ φ )=389.11*(0.776-0.484)=113.62kvar
选择
BWF10.5-30-1
型电容器进行补偿
n=113.62/30=3.787
取
n=4 则实际补偿为
Qc =30*4=120kvar (5)补偿后的计算负荷:
Q′30(1) = Q30(1) - QC =297.59-120=177.59kvar S ′(1) = P 2 30(1) + Q′2
30(1) =427.72kva
cos ′ φ = P 30(1) / S ′30(1) =389.11/427.72=0.91>0.9
3
计算电流: I 30(1) = S ′(1) / 3 Un=24.7A (6)
变压器的选择 根据
S30=427.72 kva
可选择
500V.
查《工厂供电》附录表并考虑到今后发展 的要求
:
选
SL7-630KVA 变压器一台.
低压补偿柜的选择 拟采用无功功率自动补偿屏
,装在变电所低压母线集中补偿. 从《工厂常
用电气设备手册》选用总电容容量为
360KVA 电容屏型号: PGj1 型低压无功功率自动补偿
屏有
1, 2,3,4
等
4 种方案.
其中之
l,2 屏为主屏,3,4 屏为辅屏.1,3
屏各有
6 支路,电容器为
Bw0.4—14—3 型,
每屏共
84kvA,
采用
6 步控制,
每步投入
14kVA.2,4
屏各有
8 支路,电
容器 亦为
BW0.4—14—3 型,
每屏共
112kVA,
采用
8 步控制,
每步投入
14kVA.
选 择步
骤
:① 根据控制步数要求,
选择
1
台
1
号或
2 号主屏.②
根据所需无功补偿 容量再补充
1 台
或数台
3
号或
4 号辅屏.
表全厂变电所负荷计算 设备名称 金工车间 车床 起重机 车间照明
小 计 冷作车间 装配车问 仓 库 户外照明 小 计 变电所低压 荷取
K ∑ p =0.9 K ∑ q =0.9
补偿电容
382.1 269.53 467.6 17 14 3 99.75 82.2 17.28 0. 25 0. 15 l 台数
Pe /kW Kd
cos
tan
P 30 /kw
Q 30 /kvar
S 30 /kVA
0.5 l
1.73 0
0.5 1.73
24.94 12.33 17.28 54.55 250 80 20 20 370